Testo 420
Air Flow Capture Hood Light (2.9 kg)
The volume flow hood testo 420 is light, precise and convenient solution for regulating volume flows at larger air intakes and outlets. At swirl outlets in particular, the flow straightener significantly reduces the usual measurement errors. This allows users to fulfil hygienic Indoor Air Quality guidelines and stipulations in ventilation and air conditioning systems quickly and precisely, e.g. in industry, office rooms or in cleanrooms.
Handling is especially easyith a uniquely low weight of less than 2.9 kg and ergonomic handles. The measuring instrument can be tilted and removed for more comfortable readout of the measurement values. In addition to this, mobile devices can be used via Bluetooth App integration as a second display and remote control. This makes the use of a tripod for high ceilings especially secure and comfortable. Users can furthermore use the App to finalize and send the measurement report directly on site.
-
- 80 to 3500M³/h
Applications
Air Quality & Control – Industry – Hygiene – Healthcare
TESTO 420
|
|
Temperature – NTC | |
Measuring range | -20 to +70°C |
Accuracy | ±0.5°C (0 to +70°C)
±0.8°C (-20 to +0°C) |
Resolution | 0.1°C |
Reaction time | 45s (t90) |
Humidity – Capacitive | |
Measuring range | 0 to 100 %RH |
Accuracy | ±1.8 %RH + 3 % of mv at +25°C
(5 to 80 %RH) |
Resolution | 0.1 %RH |
Differential Pressure – Piezoresistive | |
Measuring range | -120 to +120 Pa |
Accuracy | ±2% of mv + 0.5 Pa at +22°C, 1013 hPa |
Resolution | 0.001 Pa |
Reaction time | 1 s (t90) |
Absolute Pressure | |
Measuring range | 700 to 1100 hPa |
Accuracy | ±3 hPa |
Resolution | 0.1 hPa |
Reaction time | 1 s |
General technical data | |
Battery life | 40 h |
Interface | Micro-USB; Bluetooth® 4.0 wireless technology |
Memory | 2 GB (internal) |
- Overview
-
Testo 420
Air Flow Capture Hood Light (2.9 kg)
The volume flow hood testo 420 is light, precise and convenient solution for regulating volume flows at larger air intakes and outlets. At swirl outlets in particular, the flow straightener significantly reduces the usual measurement errors. This allows users to fulfil hygienic Indoor Air Quality guidelines and stipulations in ventilation and air conditioning systems quickly and precisely, e.g. in industry, office rooms or in cleanrooms.
Handling is especially easyith a uniquely low weight of less than 2.9 kg and ergonomic handles. The measuring instrument can be tilted and removed for more comfortable readout of the measurement values. In addition to this, mobile devices can be used via Bluetooth App integration as a second display and remote control. This makes the use of a tripod for high ceilings especially secure and comfortable. Users can furthermore use the App to finalize and send the measurement report directly on site.
-
- 80 to 3500M³/h
Applications
Air Quality & Control – Industry – Hygiene – Healthcare
-
- Technical Specifications
-
TESTO 420
Temperature – NTC Measuring range -20 to +70°C Accuracy ±0.5°C (0 to +70°C) ±0.8°C (-20 to +0°C)
Resolution 0.1°C Reaction time 45s (t90) Humidity – Capacitive Measuring range 0 to 100 %RH Accuracy ±1.8 %RH + 3 % of mv at +25°C (5 to 80 %RH)
Resolution 0.1 %RH Differential Pressure – Piezoresistive Measuring range -120 to +120 Pa Accuracy ±2% of mv + 0.5 Pa at +22°C, 1013 hPa Resolution 0.001 Pa Reaction time 1 s (t90) Absolute Pressure Measuring range 700 to 1100 hPa Accuracy ±3 hPa Resolution 0.1 hPa Reaction time 1 s General technical data Battery life 40 h Interface Micro-USB; Bluetooth® 4.0 wireless technology Memory 2 GB (internal) - Downloads